- 12 -
5. Auto Air control
• The indoor fan speed is shifted from low to high by the difference of room temp. and setting temp.
• The fan speed selected isnot changed for 2 minutes at least.
• The operation diagrams are shown as following.
■  
Cooling mode
■  
Heating mode
COMP ON + 0.5°C
COMP ON
(SET TEMP + 0.5°C)
COMP OFF
(SET TEMP - 0.5°C)
COMP OFF
(SET TEMP)
COMP OFF
(SET TEMP +3°C)
SET TEMP
SET TEMP +
2°C
INDOOR FAN
CONPRESSOR
COMPRESSOR
SET FAN
SPEED
ON
ON
ON
ON
ON
OFF
OFF
ON
HOTSTART
CONTROL
HIGH
INDOOR PIPING TEMP.: 35°C
HOT START
COMPLETION 
POINT
20SEC
20SEC
30SEC
HIGH
MED
MED
LOW
LOW
LOW
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
HIGH
MED
LOW)
LOW
LOW
LOW
MED
ROOM TEMP.
INDOOR FAN
- 13 -
COMP. OFF
(SET TEMP +3°C)
COMP. ON
(SET TEMP.)
20SEC
30SEC
MAX. 4 MIN
30SEC
30SEC
20SEC
HOT
START
CONTROL
COMPRESSOR
INDOOR FAN
ROOM TEMP
OFF
OFF
ON
ON
ON
ON
L
O
W
L
O
W
L
O
W
L
O
W
L
O
W
O
F
F
O
F
F
SELECTING
FNA SPEED
SELECTING
FAN SPEED
SELECTING
FAN SPEED
6. Heating Mode Operation
• The unti will be operted according to th setting tempo. by using a remote controller and the operation diagram
is as following.
• When the compressor is not operated by setting temp, indoor fan is stopped but operated again for 3 mins at
intervals of 3 minutes automatically.
In heating mode, fan operation mode is not operated during the compressor in ON.
7. Hot-Start Control (Heating)
• The indoor fan stops until the evaporator piping temperate will be reached 26°C (BY TEMPERATURE).
• The indoor fan operates when 4 mins passed, even if the evaporator piping temperature is not reached 26°C.
(BY TIME).
• The operation diagram is as following.
PIPING
TEMP 26°C
INDOOR
FAN
COMPRESSOR
(HOT-START BY TEMPERATURE)
(HOT-START BY TIME)
ON
ON
COMPRESSOR
OFF
LOW
SELECTING
FAN SPEED
SELECTING
FAN SPEED
LOW
OFF
INDOOR
FAN
PIPING
TEMP 26°C
4MINS
30SEC
30SEC
- 14 -
8. Deicer Control
• Deicing operation is controlled by timer and sensing the outdoor piping temperature in heating operation mode.
• The first deicing starts when 60 minutes or more passed after starting of heating operation and the outdoor
piping temperature is -6°C or lower. 
• Deicing ends after 12 minutes or when the outdoor piping temperature is 12 or higher.
• Heating operation is repeated automatically 60 min. Heating and 12min. Deicing after the first deicing ends.
• The operation diagram is as following.
• In deicing operation, only solenoid valve of the indoor unit operated at that time is ON.
9. Forced operation
• If you lose wireless remote controller, you can operate the unit with forced operation switch.
• When you operate the unit with forced operation switch, the unit isn't always operated in operation mode which
you desire. So you can operate in uour operation mode by only remote controller.
• The standard conditions are as following :
The outdoor
piping Temp.
12°C
DEICING OFF
-6°C 
DEICING ON
COMPRESSOR
4-WAY VALVE
ON
INDOOR FAN
ON
OUTDOOR FAN
ON
ON
ON
ON
ON
ON
LOW
MORE THAN
60MINS
Deicing
Deicing
12MINS
60MINS
12MINS
30 SEC
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
Selecting
fan speed
Cooling
Model
Operation Mode
FAN Speed
Setting Temp.
Heat pump
Room Temp 
24°C
21°C 
Room Temp < 24°C
Room Temp <21°C
Cooling
Cooling
Soft Dry
Heating
High
High
High
High
24°C
24°C
25°C
22°C
- 15 -
10. Micom dehumidify
• In order to raise the efficiency of dehumidify, "Restarting temperature of compressor operation" set higher 1°C
than setting temperature.
• When room temperature is higher than "Restarting temperature of compressor operation", it will be operate by
fan speed setting.
• When room temperature reach "Stopping temperature of compressor operation", the fan and the compressor
will be stop. After 5mins passed, only fan start to operate in low mode for 2 min.
• When room temperature is between "Restarting temperature of kcompressor operation" amd "Stopping
temperature of compressor operation", operate micom dehumidify mode for 10 mins and fan operate low
speed.
• Fan will be stop after 10mins passed to operate imcom dehumidify or below or "Stopping temperature of com-
pressor operation" after 4 mins.
• When 5 mins passed after stopping compressor, fna start to low mode and 7 mins passed after stopping,
compressor start to operate micom dehumidify again. (When micom dehumidify operate, fan will operate at
low speed.)
• When room temperature is below of "Stopping temperature of compressor operation", fan will stop 5 mins and
operate 2 min in low mode.
• In micom dehumidify mode, control of fan speed is as following.
ROOM TEMP.
COMP ON
(SET TEMP. +1°C)
COMP. OFF
(SET TEMP. -1°C)
INDOOR FAN
COMPRESSOR
ON 
OFF
ON
ON
OFF
ON
2MINS
5MINS
5MINS
5MINS
10MINS
10MINS
MAX 4MINS
10MINS
OPERATION
COOLING
DELAY 3 MINS
OPERATION
COOLING
2 MINS
2MINS
MAX
OFF
FAN SPEED
SETTING
LOW
LOW
LOW
LOW
OFF
OFF
OFF
LOW
LOW