DOWNLOAD LG LM-3060HL Service Manual ↓ Size: 1.42 MB | Pages: 72 in PDF or view online for FREE

Model
LM-3060HL
Pages
72
Size
1.42 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
lm-3060hl.zip
Date

LG LM-3060HL Service Manual ▷ View online

Temperatura
Bassa
Alta
CHAOS
ON
OFF
SET
CANCEL
RESET
• Cooling Operation Mode.  (     )
• Heating Operation Mode.  (     )
• Soft Dry Operation Mode.  (     )
• Auto Operation Mode.   (     )
- 4 -
Remote Controller
Operation ON/OFF
(LOW)
(MED)
(HIGH)
(AUTO)
Down to 20°C
UP to 30°C
Down to 16°C
UP to 30°C
Cooling
Heating
: OFF, ON, OFF        ON
: Cancel Sleep Mode, Timer ON or Timer OFF.
: 1, 2, 3, 4, 5, 6, 7, Off Timer 
Operation Mode Selection
Fan Speed Seleciton
Room Temperature Display
Temperature Setting
: HIGH: 40°C             LOW: 19°C
Setting the Time or Timer
Timer Selection
Timer Setting
Timer Cancel
Sleep Operation
Airflow Direction Control
Reset
A
B
C
A
B
- 19 -
Installation
1. Installation of Indoor, Outdoor unit
1) Selection of the best location
1. Indoor unit.
• There should not be any heat source or steam near
the unit.
• There should not be any obstacles to prevent the air
circulation.
• A place where air will be circulated well.
• A place can be drained easily.
• A place where noise prevention is taken into
consideration.
• Do not install the unit near the door way.
• Ensure the spaces from the wall, ceiling, fence or
other obstacles.
The spaces are indicated by arrows.
2. Outdoor unit.
• If an awning is built over the unit to prevent being
exposed sunlight or rain directly, heat radiation from
the condenser should be not restricted.
• There should not be any animals or plants which
could be affected by not air discharged.
• Ensure the spaces from the wall, ceiling, fence or
other obstacles.
The spaces are indicated by arrows.
3. Piping length and the elevation.
More than
5cm
More than 5cm
Rear left
left
Right
Down right
Rear right
Front
More
than 5cm
More than eye-level
More than 10cm
More than 10cm
More than 70cm
Indoor unit
Outdoor
unit
Pipe Size
LIQUID
GAS
A-UNIT
1/4"
1/2"
15
5
B/C-UNIT
1/4"
3/8"
15
5
Max. piping
length
A (m)
Max.
Elevation
B (m)
4. Additional refrigerant charge (R-22, g) 
(In case of installating 3-UNIT).
• You should charge the refrigerant additionally, if total
length of pipe is over 20m.
CALCULATION: 30g x (L-20)/m
(L: total length of pipe)
- 28 -
A
B
C
1) Checking the Drainage
1. Remove the Grille from the cabinet.
• Set the up-and-down louver to open position
(horizontally) by finger pressure.
• Remove the screw caps and the securing screws.
• To remove the Grille, pull the lower left and right
side of the grille toward you (slightly titled) and lift it
straight upward (Two tabs on the top inside edge of
the grille are clear of their slots).
2. Check the drainage.
• Pour a glass of water on the evaporator.
• Ensure if water flows drain hose of indoor unit.
4. Checking the Drainage and Connecting the cable to Indoor unit
Push on the right and the left side.
Screw cap (both the left and the right side))
Screw (both the left and the right side)
- 29 -
2) Connect the cable to the indoor
unit
1. Connect the wires to the terminals on the control
panel individually according to the outdoor unit
connection.
• Ensure the color of cables of outdoor unit and the
terminal No.s are the same to the indoor's
respectively.
• Secure the cable onto the control board with the
holder (clamper)
2. Attach the Grille onto the cabinet
• Grasp the lower left and right side of the Grille and
engage two tabs on the top inside edge of the grille
with two slots on the cabinet's top front edge.
• Press the Grille toward to the cabinet until it will be
back into place.
• Secure the grille to the cabinet with two screws.
ø
7
m
m
ø
7
m
m
Connecting cable
Signal cable
The connecting and signal cable, from the indoor
unit to the outdoor unit should be complied with the
following specification. (Rubber insulation, type
H05RN-F approved by TUV or VDE)
NOMINAL CROSS-
SECTIONAL AREA
0.75 mm
OR MORE
(Morsettiera unità esterna)
1(BK)
[Unità A/B/C]
[Unità A]   [Unità B/C]  Alimentazione elettrica
2(WH)3(GN)
1(BK)
SIGNAL  CABLE
(DC 5V)
CONNECTOR CABLE
(AC POWER)
SIGNAL  CABLE
(DC 5V)
CONNECTOR CABLE
(AC POWER)
SIGNAL  CABLE
(DC 5V)
CONNECTOR CABLE
(AC POWER)
2(WH)
1(BR) 2(BL)
3(GN)
1(BK) 2(WH)
1(BR) 2(BL)
3(GN)
1(BK) 2(WH)
1(BR) 2(BL)
3(GN)
1(BR) 2(BL) 1(BR) 2(BL)
2(BK)
1(WH)
(Morsettiera unità interna)
Unità A
Unità B
Unità C
Cavo di alimentazione
BLACK
BLUE
GREEN
GN/YL
(SIGNAL CABLE)
(CONNECTING CABLE)
WHITE
BROWN
Page of 72
Display