- 47 -
(5) Air Purging of the Pipings and indoor unit
The air which contains moisture remaining in the is refrigeration cycle may cause a malfunction on the 
compressor.
1. Confirm that both the liquid side valve and the gas side valve are set to the closed position.
2. After connecting the piping, check the joints for gas leakage with gas leak detector.
3. Remove the service port nut, and connect the gauge manifold and the vacuum pump to the service port
by the charge hose.
4. Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below-76cmHg.
5. Disconnect the charge hose and fit the nut to the service port.
(Tightening torque: 1.8kg.m)
6. Remove the valve stem nuts, and fully open the stems of the 2-way and 3-way valves with a hexagon
wrench.
7. Tighten the valve stem nuts of the 2-way valve and 3-way valve.
Indoor unit
Outdoor unit
Liquid side
Gas side
CLOSE
OPEN
Vacuum pump
2-way
valve
Closed
Closed
3-way
valve
- 48 -
(7) Maximum Length of Pipe and Freon Extra Charge
INDOOR UNIT
INDOOR UNIT
OUTDOOR UNIT
B(Length)
D(Length)
A(Height)
C(Height)
Capacity
STANDARD
CONNECTION TYPE
Charge am't(g)
(Btu/h)
LENGTH(m)
A
B
C
D
per 1m
~7000
7.5
7
15
7
15
20
~9000
7.5
7
15
7
15
20
~12000
7.5
7
15
7
15
20
~18000
7.5
7
15
7
15
40
~24000
7.5
7
15
7
15
40
** A, B mean indoor unit higher located than outdoor unit.
C, D mean outdoor unit higher located than indoor unit.
Charge amount per 1m
(6) Preventive function of cable mis-connection(Cooling & Heating)
This product has a preventive function of cable mis-connection. In case of mis-connection (in case that the
cables between indoor and outdoor units have not been connected properly), it gives a warning signal of LED
flickering 3 minutes after starting operation. (Press the forced operation key more than 3 seconds.)
CAUTION
Don't turn on all the indoor units all at once when you check the connection status. In that case the sensor can
not be operated properly.
Once
3 seconds
Twice
3 seconds
Once
3 seconds
Twice
- 49 -
(8) Test running
Battery Cover
Discharge air
Bolt
Tubing connection
Settlement of Outdoor Unit
• Anchor the outdoor unit with a bolt and nut
(ø10cm) tightly and horizontally on a concrete or
rigid mount.
• When installing on the wall, roof or rooftop,
anchor the mounting base securely with a nail or
wire assuming the influence of wind and earth-
quake.
• In the case when the vibration of the unit is con-
veyed to the house, settle the unit with an anti-
vibration rubber.
2) Evaluation of the performance
1. Measure the temperature of the intake and
discharge air.
2. Ensure the difference between the intake
temperature and the discharge one is more
than 8°C.
1) Connection of power supply
1. Connect the power supply cord to the inde-
pendent power supply.
2. Prepare the remote control.
• Insert two batteries provided.
Remove the battery cover from the remote con-
troller.
• Slide the cover according to the arrow direction.
Insert the two batteries.
(Two "R03" or "AAA" dry-cell batteries or equiv-
alent.)
• Be sure that the (+) and (-) directions are cor-
rect.
• Be sure that both batteries are new.
Re-attach the cover.
• Slide it back into position.
3. Operate the unit at cooling operation mode
for fifteen minutes or more.
- 37 -
2) Indoor Unit Installation
The mounting wall should be strong and solid
enough to protect it from the vibration.
1. Mount the installation plate on the wall with
four Type "A" screws.
(If mounting the unit on the concrete wall, consid-
er using anchor bolts.)
• Always mount the Installation plate horizontally
by aligning the marking-off line by means of the
thread and a level.
2. Drill the piping hole with 70mm dia. holecore
drill.
• Line according to the arrows marked on lower
the left and the rght side of the Installation Plate.
The meeting point of the extended line is the
center of the hole.
• Drill the piping hole at either the right or the left
and the hole should be slightly slant to the out-
door side.
Installation Plate
marking-off line
Thread
Weight
Type "A" screw
ø70mm
ø70mm
5
~
7
m
m
A
A
A
A
ø70mm
ø70mm
50mm
20
m
m
20
m
m
80mm
Indoor
Outdoor
Wall
Left rear piping
Right rear piping
Left rear piping
Right rear piping
The lower left and the right side of
Installation Plate
6K, 7K, 8K, 9K Btu
9K, 10K, 12K Btu