–6–
Power Source
Ø, V, Hz"
Cooling
Capacity
kcal/h(BTU/h)
W
Input
W
Heating
Capacity
kcal/h(BTU/h)
W
Input
W
Rated Load Amp.
Cooling
A
Heating
A
Air Volumn
Cooling(H/M/L)
CMM(m
3
/min)
Heating(H/M/L)
Refrigerant(R-22)
g
Drain Hose
In. Dia
mm
Main Cable
No. X mm
2
Connecting Cable
Remote Control Type
Refigerant Control Type
Fuction
Soft Dry
Timer
Self Diagnosis
Deice Operation
Hot Start
Zone Control(Optional)
Central Control(Optional)
Group Control(Optional wiring)
Weekly Programning
Thermistor
Drain Pump
Auto changeover(Auto Operation: CL)
Stand-by Consumption 0
Phase Control
Tele Control(Optional)
PLASMA(Optional)
Connecting Pipe
Liquid
Inch
Gas
(mm)
Dimension
Indoor
mm
Outdoor
(WxDxH)
Net
Indoor
Kg
Weight
Outdoor
3, 380-415, 50
3,380-415, 50
9,072(36,000)
9,072(36,000)
10,548
10,548
4,000
4,000
9,072(36,000)
-
10,548
-
3,300
-
7.2
7.2
6.3
-
32/29/26
32/29/26
32/29/26
-
1,840
1,800
22.6
22.6
4*2.5
4*2.5
5*0.75
4*0.75
L.C.D Wired
L.C.D Wired
Capillary type
Capillary type
Yes
Yes
24 Hours On/Off
24 Hours On/Off
Yes
Yes
Yes
-
Yes
-
Optional
Optional
Optional
Optional
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Optional
Optional
Optional
Optional
1/4(6.35)
1/4(6.35)
5/8(15.88)
5/8(15.88)
1180*450*298
1180*450*298
870*320*800
870*320*800
38
38
72
72
Model
LB-G3680HL
LB-G3680CL
Dimensions
–7–
W
H
D
(1) Indoor Unit
MODEL
DIM
W(mm)
880
880
1180
H(mm)
260
260
298
D(mm)
450
450
450
18K
24K
36K
(2) Outdoor Unit
–8–
H
W
D
(18K/24K/36K)
MODEL
DIM
W(mm)
870
870
870
H(mm)
655
655
800
D(mm)
320
320
320
18K
24K
36K
Refrigeration Cycle Diagram
• HEAT PUMP (LB-H1860HL / LB-H2460HL / LB-G3680HL)
• Rated performance for refrigerant line length of: 7.5m
• If 18K Model is installed at a distance of 15m, 255g of refrigerant should be added (15-7.5)x30g=225g
• If 18K Model is installed at a distance of 15m, 255g of refrigerant should be added (15-7.5)x30g=225g
–9–
INDOOR UNIT
OUTDOOR UNIT
HEAT
EXCHANGER
EXCHANGER
HEAT
EXCHANGER
EXCHANGER
COMPRESSOR
GAS SIDE
LIQUID SIDE
COOLING
HEATING
REVERSING
VALVE
VALVE
CAPILLARY TUBE
LB-H1860HL
5/8"
1/4"
7.5
50
5
30
30
LB-H2460HL
5/8"
1/4"
7.5
50
5
30
35
LB-G3680HL
5/8"
1/4"
7.5
50
5
30
45
*Additional
refrigerant
(g/m)
Pipe size(Diameter: ø)
Piping length(m)
Elevation(m)
MODEL
Gas
Liquid
Rated
Max.
Rated
Max.
Click on the first or last page to see other LB-H1860HL_CL / LB-H2460HL_CL / LB-G3680HL_CL service manuals if exist.