LG LB-D1861HL_CL / LB-D2461HL_CL / LB-F3061HL / LB-F3661HL_CL / LB-F3681HL_CL / LB-F4261HL / LB-E4881HL_CL / LB-E6081HL_CL Service Manual ▷ View online

Electronic Parts Troubleshooting Guide
: The unit does not operate.
Possible Trouble 1
–40–
YES
NO
YES
Is the input voltage
of transformer AC230V?
Check the FUSE
and the wiring diagram.
Is the PIN 49,58 of
MICOM. DC5V?
Exchange MICOM. 
YES
NO
Check the main P.C.B
pattern.
NO
YES
Is the output voltage 
of IC03D DC5V?
NO
Exchange IC03D.
Is the input voltage
of IC03D about AC12V?
Check the 
5V P.C.B pattern.
Possible Trouble 2
: The indoor fan does not operate.
–41–
NO
NO
Is it the HOT
START mode?
Is IC01M operated
normally?
Check the fan motor
and connector.(CN-MOTOR)
YES
Is the each Relay
any problem?
YES
NO
YES
It is normal operation.
Exchange IC01M.
Exchange Relay.
YES
YES
NO
YES
Is it Heating Mode?
Does the temperature 
set all right?
Change IC01M.
NO
NO
Adjust operation mode.
Adjust set temperature.
Is IC01M operated 
normally?
YES
Check the connector.
(CN-OUT)
Check RY-4Way.
NO
Is 4way-valve operated?
Possible Trouble 3
: Ineffective Heating
–42–
Possible Trouble 4
: Wired remote controller does not operate.
NO
YES
YES
YES
Is the LCD operated
normally?
Is the terminal of wired
Remocon T2 DC12V?
Is the pin 39, 40 of
Micom DC 5V?
Change the wired Remocon.
Check the wired Remocon 
PCB and DC 12V pattern.
NO
NO
Check the parts of 
communication.
Connector CN-Remo, and 
terminals of wired 
Remocon exactly.
Product Specifications (Cooling & Heating) 
–5–
Power Source
Ø, V, Hz"
Cooling
Capacity
kcal/h(BTU/h)
W
Input
W
Heating
Capacity
kcal/h(BTU/h)
W
Input
W
Rated Load Amp.
Cooling
A
Heating
A
Air Volumn
Cooling(H/M/L)
CMM(m
3
/min)
Heating(H/M/L)
Refrigerant(R-22)
g
Drain Hose
In. Dia
mm
Main Cable
No. X mm
2
Connecting Cable
Remote Control Type
Refigerant Control Type
Fuction
Soft Dry
Timer
Self Diagnosis
Deice Operation
Hot Start
Zone Control(Optional)
Central Control(Optional)
Group Control(Optional wiring)
Weekly Programning
Thermistor
Drain Pump(Optional)
Auto changeover(Auto Operation: CL)
Stand-by Consumption 0
Connecting Pipe
Liquid
Inch
Gas
(mm)
Dimension
Indoor
mm
Outdoor
(WxDxH)
Net
Indoor
Kg
Weight
Outdoor
1, 220-240, 50
1, 220-240, 50
1, 220-240, 50
1, 220-240, 50
4,536(18,000)
4,536(18,000)
6,048(24,000)
6,048(24,000)
5,274
5,274
7,033
7,033
1,950 2,050
2,600 2,800 
4,536(18,000)
-
6,048(24,000)
-
5,274
-
7,033
-
1,900
-
2,500
-
9.4
9.5
12
13
9.0
-
11
-
16.5/14.5/12.5
16.5/14.5/12.5
16.5/14.5/12.5
16.5/14.5/12.5
16.5/14.5/12.5
-
16.5/14.5/12.5
-
1,900 1,400  2,270 1,500 
22.6
22.6
22.6
22.6
3*2.5
3*2.5
3*2.5
3*2.5
6*0.75
4*0.75
6*0.75
4*0.75
L.C.D Wired
L.C.D Wired
L.C.D Wired
L.C.D Wired
Capillary type
Capillary type
Capillary type
Capillary type
Yes
Yes
Yes
Yes
24 Hours On/Off
24 Hours On/Off
24 Hours On/Off
24 Hours On/Off
Yes
Yes
Yes
Yes
Yes
-
Yes
-
Yes
-
Yes
-
Optional
Optional
Optional
Optional
Optional
Optional
Optional
Optional
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Optional
Optional
Optional
Optional
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
1/4(6.35)
1/4(6.35)
1/4(6.35)
1/4(6.35)
5/8(15.88)
5/8(15.88)
5/8(15.88)
5/8(15.88)
880*575*281
880*575*281
880*575*281
880*575*281
870*320*655
870*320*655
870*320*655
870*320*655
42
42
42
42
57
55
60
57