LG LB-D1861HL_CL / LB-D2461HL_CL / LB-F3061HL / LB-F3661HL_CL / LB-F3681HL_CL / LB-F4261HL / LB-E4881HL_CL / LB-E6081HL_CL Service Manual ▷ View online

Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Auto Operation(Auto Change Over)
Deice (defrost) control (Heating)
Auto Restart
–3–
Hot-start Control (Heating)
• The indoor fan stops until the evaporator piping tempera-
ture will be reached at 28°C.
High head height Drain pump(Optional)
• A standard drain-head height of up to 700mm is possible.
Central Control(Optional)
• It is operating individually or totally by central control function.
Group Control(Optional Wiring)
• Each controller can control 16 units and 8 controllers can connect.
• It operates maximum 16 units by only one wired remote con-
troller and each unit starts random to prevent overcurrent.
• Room temperature sensor. (Thermistor)
• Maintains the room temperature in accordance with the Setting Temp.
• Indoor fan is delayed for 5 seconds at the starting.
• Restarting is inhibited for approx. 3 minutes.
• High, Med, Low
• Intermittent operation of fan at low speed.
• Although the air-conditioner is turned off by a power failure, it is restarted automati-
cally previous operation mode after power supply.
• The setting temperature and desired operation mode are auto-
matically set by fuzzy rule.
• Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.
–4–
Remote Controller
Operation ON/OFF
Operation Mode Selection
Fan Speed Selection
Room Temperature Display
Temperature Setting
Setting the Timer 
Weekly Program
(Cooling 
model only)
(Heating 
model only)
(Low)
(Med)
(High)
Cooling Operation Mode (       )
Heating Operation Mode (       )
Auto Operation Mode (       )
Soft Dry Operation Mode (       )
Fan Operation Mode
HI
AUTO
MED
LO
Program
Holiday
SET/CLR
Min
Hour
Week
Timer
Cancel
Timer
Cancel
: High:39°C 
LOW:11°C
: Fan Operates without cooling & heating
Cooling
Heating 
Down to 18°C
Up to 30°C
Down to 16°C
Up to 30°C
–22–
Installation of Indoor, Outdoor Unit
1. Selection of the best location
1) Indoor unit 
Select location
Install the air conditioner in the location that satis-
fies the following conditions.
• The place shall easily bear a load exceeding four
times the indoor unit’s weight.
• The place shall be able to inspect the unit as the
figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suit-
able dimension “H” is necessary to get a slope to
drain as figure.)
• The place shall easily connect with the outdoor
unit.
• The place where the unit is not affected by an
electrical noise.
• The place where air circulation in the room will be
good .
• There should not be any heat source or steam
near the unit.
2) Outdoor unit
• If an awning is built over the unit to prevent direct
sunlight or rain exposure, be careful that heat
radiation from the condenser is not restricted. 
• There should not be any animals or plants which
could be affected by hot air discharged. 
• Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
3) Piping length and the elevation
Indoor unit
Outdoor unit
B
A
More than
30cm
More than
30cm
More than
70cm
Sunr
oof
Fence or
obstacles
Top view
(unit: mm)
H
Front view
600
600
Front
Inspection hole
(600X600)
Control box
1000
• If 18K Model is installed at a distance of 15m, 
188g of refrigerant should be added (15-7.5) x 25g = 188g
• Capacity is based on standard length and maximun allowance length is on the basis of reliability.
18K BTU/h
5/8"
5/8"
5/8"
1/4"
7.5
50
5
30
25
30K BTU/h
5/8"
3/8"
7.5
50
5
30
50
42K BTU/h
3/4"
3/8"
7.5
50
5
30
50
H/P
1/4"
7.5
50
5
30
30
5/8"
3/8"
7.5
50
5
30
40
5/8"
3/8"
7.5
50
5
30
40
C/O
H/P
C/O
1/4"
7.5
50
5
30
30
30
25
48K BTU/h
3/4''
3/8"
7.5
50
5
50
3/4"
1/2"
7.5
50
5
60
60K BTU/h
24K
BTU/h
36K
BTU/h
Capacity
Gas
Liquid
Elevation B(m)
Length A(m)
* Additional
refrigerant
(g/m)
Pipe Size
(Diameter: Ø)
Standard
Standard
Max.
Max.
–31–
• Drill the piping hole with 70mm dia, hole
core drill.
• Piping hole should be slightly slant to the
outdoor side.
INSULATION, OTHERS
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
INDOOR UNIT
REFRIGERANT PIPE
• Insulate and tape both the gas piping and liquid piping.
THERMAL INSULATION
5~7mm
Indoor
Outdoor
WALL
Make sure that there is no clearance here.
Overlap with thermal
insulator for piping.
Thermal insulator for refrigerant pipe
(Local supply)
Thermal insulator for
piping(Local supply)
Hose crip for thermal insulator(Local supply)
Union for liquid pipe
Refrigerant pipe and thermal
insulator(Local supply)
Union for gas pipe
Thermal insulator for refrigerant pipe
(Local supply)
Hose crip for thermal insulator
(Local supply)
Connecting cable
Liquid pipe
Thermal insulator
Gas pipe
Tape
Page of 62
Display

LG LB-D1861HL_CL / LB-D2461HL_CL / LB-F3061HL / LB-F3661HL_CL / LB-F3681HL_CL / LB-F4261HL / LB-E4881HL_CL / LB-E6081HL_CL Service Manual ▷ Download

  • DOWNLOAD LG LB-D1861HL_CL / LB-D2461HL_CL / LB-F3061HL / LB-F3661HL_CL / LB-F3681HL_CL / LB-F4261HL / LB-E4881HL_CL / LB-E6081HL_CL Service Manual ↓ Size: 1.69 MB | Pages: 62 in PDF or view online for FREE
  • Here you can View online or download the Service Manual for the LG LB-D1861HL_CL / LB-D2461HL_CL / LB-F3061HL / LB-F3661HL_CL / LB-F3681HL_CL / LB-F4261HL / LB-E4881HL_CL / LB-E6081HL_CL in PDF for free, which will help you to disassemble, recover, fix and repair LG LB-D1861HL_CL / LB-D2461HL_CL / LB-F3061HL / LB-F3661HL_CL / LB-F3681HL_CL / LB-F4261HL / LB-E4881HL_CL / LB-E6081HL_CL Air Conditioner. Information contained in LG LB-D1861HL_CL / LB-D2461HL_CL / LB-F3061HL / LB-F3661HL_CL / LB-F3681HL_CL / LB-F4261HL / LB-E4881HL_CL / LB-E6081HL_CL Service Manual (repair manual) includes:
  • Disassembly, troubleshooting, maintenance, adjustment, installation and setup instructions.
  • Schematics, Circuit, Wiring and Block diagrams.
  • Printed wiring boards (PWB) and printed circuit boards (PCB).
  • Exploded View and Parts List.