DOWNLOAD LG LB-D1861 / LB-D2461 / LB-F3061 / LB-F3661 / LB-F3681 / LB-F4261 / LB-E4881 / LB-E6081_HL_CL_HP_CP Service Manual ↓ Size: 1.62 MB | Pages: 61 in PDF or view online for FREE

Model
LB-D1861 LB-D2461 LB-F3061 LB-F3661 LB-F3681 LB-F4261 LB-E4881 LB-E6081_HL_CL_HP_CP
Pages
61
Size
1.62 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
lb-d1861-lb-d2461-lb-f3061-lb-f3661-lb-f3681-lb-f4.zip
Date

LG LB-D1861 / LB-D2461 / LB-F3061 / LB-F3661 / LB-F3681 / LB-F4261 / LB-E4881 / LB-E6081_HL_CL_HP_CP Service Manual ▷ View online

–35–
2) Group Control(Optional Wiring)
• You can use a group control operation after connecting the brown and yellow wire of each  air-conditioner.
• Remove the resistor "OP 7" in remote controller.
• It operates maximum 16 Units by only one Wired Remote Controller,
and each Unit starts sequentially to prevent overcurrent.
Wiring design
Features
• Use Only One Wired Remote Controller with several air conditioners(max. 16 Units)
• Random starting to prevent overcurrent.
Operation unit
ZONE
1 2 3 4
Humidify
JET
AUTO
AUTO SWING
OPERATION
FAN SPEED
Program set
SUB FUNCTION
SET TEMP
Room Temp
HI
MED
LO
Heater
Defrost
Filter
Preheat
Out door
Time
Timer
On
Set no. Time
Off
01
03
05
07
09
11
13
15
17
19
21
23
Indoor Unit 1
Terminal(Local Supply)
Block
Terminal(Local Supply)
Block
Terminal(Local Supply)
Block
Main PCB
#1
Main PCB
#2
Main PCB
#16
Wired Remote Controller
Slide Switch
OP7
Remote
Controller
PCB
Indoor Unit 2
Main PCB
Indoor Unit 16
Connector
RED(12V)
YL(SIGNAL)
BR(GND)
RED(12V)
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
Connecting Cable(Local Supply)
Connector
Connector
....
....
• Be careful not to exchange the color of wires.
• The maximum length of connecting wire should be below 200m(25
) on connecting each units.
• Use a wire more than 0.5mm
2
CAUTION
2. Ceiling dimension and hanging
bolt location
Installation of Unit
Install the unit above the ceiling correctly.
• Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
• Apply a filter Accessory at air return hole.
• Install the unit leaning to a drainage hole side as a
figure for easy water drainage.
• A place where the unit will be leveled and that can
support the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
–23–
CASE 1
POSITION OF SUSPENSION BOLT
CASE 2
POSITION OF CONSOLE BOLT
(Unit:mm)
Drainage hole
M10 Nut
M10 SP. washer 
M10 washer 
X 4
X 4
(Local
supply)
X 4
M10 Nut
M10 SP. washer 
M10 washer 
X 4
X 4
(Local
supply)
X 4
A
B
C
1-3 mm
D
(G)
H
I
E
F
A
B
C
D
E
F
(G)
H
I
18K BTU/h 942 880 466
54
575
30
87
750 186
24K BTU/h 942 880 466
54
575
30
87
750 186
30K BTU/h 1242 1180 492
54
600
30
87
830 186
1072 1010 492
54
600
30
87
750 186
1242 1180 492
54
600
30
87
830 186
1242 1180 492
54
600
30
87
830 186
1292 1230 650.5 54
760
30
120 1006 294
1292 1230 570.5 54
680
30
120 1006 294
1292 1230 650.5 54
760
30
120 1006 294
1292 1230 570.5 54
680
30
120 1006 294
Dimension
Capacity
36K BTU/h
(LB-C36)
36K BTU/h
(LB-F36)
42K BTU/h
48K BTU/h
(LB-B48)
60K BTU/h
(LB-B60)
48K BTU/h
(LB-E48)
60K BTU/h
(LB-E60)
NOTE:
• Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat
exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily
steam which should not flow into the suction of the air conditioner.
• Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
–24–
3. The Indoor Unit Installation
• Select and mark the position for fixing bolts.
• Drill the hole for set anchor on the face of ceiling.
• Insert the set anchor and washer onto the suspen-
sion bolts for locking the suspension bolts on the ceil-
ing.
• Mount the suspension bolts to the set anchor firmly.
• Secure the installation plates onto the suspension
bolts (adjust level roughly) using nuts, washers and
spring washers.
4. Remote Controller Installation
• Although the room temperature sensor is in the indoor unit, the remote controller should be installed
in such places away from direct sunlight and high humidity.
Installation of the remote controller
• Select places that are not splashed with water.
• Select control position after receiving customer approval.
• The room temperature sensor is built in the indoor unit.
• This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult
to see.(The standard height is 1.2 ~ 1.5m high)
Routing of the remote controller cord
• Keep the remote controller cord away from the refrigerant piping and the drain piping.
• To protect the remote controller cord from electrical noise, place the cord at least 5cm away from other power
cables (audio equipment, television set, etc.)
• If the remote controller cord is secured to the wall, provide a trap at the top of the cord to prevent water
droplets from running.
Tighten the nut and bolt to prevent unit falling.
CAUTION
1 Set anchor
Old building
New building
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
   bolts
• Local supply
➀ 
Set anchor
Plate washer 
- M10
Spring washer
- M10
Nut 
- W3/8 or M10
Suspension bolt
- W3/8 or M10
–25–
Remote control 
box body
Cord clamp
(accessory)
Lever carefully 
the box open 
using a screw 
driver, etc.
Front case
The lo
wer par
t
Face of wall
Under plate
Screw (accessory)
Remove the battery cover from the remote con-
troller.
• Slide the cover according to the arrow direction.
Insert the two batteries.
• Be sure that the (+) and (-) directions are correct.
• Be sure that both batteries are new.
Re-attach the cover.
• Slide it back into position.
• Fix the under plate on the wall
• Separate the under plate from Remote control box.
• Fix the cord clamps on the wall by ø 3 tapping
screws (accessory).
• Fix the remote control cord.
WIRED REMOTE CONTROL INSTALLATION
REMOTE CONTROL PREPARATION(OPTIONAL)
DISASSEMBLING
ELECTRICAL WIRING
HOW TO MOUNT ONTO A WALL
HOW TO INSERT BATTERIES
 
Wire and make sure that teminal
numbers are matched on unit side and
remote controller side.
The maximum length of the cord is 100m.
If the length of the cord exceeds 50m,
use a wire size greater than 0.5mm
2
.
Remote controller
(Main board)
CN REMO
• Do not use rechargeable batteries,
such batteries differ from standard dry
cells in shape, dimensions, and per-
formance.
• Romove the batteries from the remote
controller if the air conditioner is not
going to be used for some long time.
HOW TO INSERT BATTERIES
Page of 61
Display

Click on the first or last page to see other LB-D1861 / LB-D2461 / LB-F3061 / LB-F3661 / LB-F3681 / LB-F4261 / LB-E4881 / LB-E6081_HL_CL_HP_CP service manuals if exist.