LG LB-D1860HL Service Manual ▷ View online
–9–
Operation Details
(1) The function of main control
1. Time Delay safety Control
• 3min : The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
• 30sec: The 4-way valve is ceased for 30sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode while compress is off.
While compressor is running, it takes 3~5 seconds to switch.
2. Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by Micom Control.
3. Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
Intake Air temp.
COMP. ON
(SET TEMP.+0.5°C)
(SET TEMP.+0.5°C)
COMP. OFF
(SET TEMP. -0.5°C)
(SET TEMP. -0.5°C)
More than
More than
3 minutes
3 minutes
Selecting
Selecting
Selecting
fan speed
fan speed
fan speed
COMPRESSOR
ON
OFF
ON
OFF
ON
INDOOR FAN
Low Low
Intake Air temp.
Setting temp.+3°C
(Compressor OFF)
Setting temp.
(Compressor ON)
(Compressor ON)
INDOOR FAN
Low
OFF Low
Low
OFF
COMPRESSOR
ON
OFF
ON
OFF
• A point;
While the indoor Heat-Exchanger temperature is higher than 40°C fan operates at low speed, when
it becomes lower than 35˚C fan stops.
• B point;
When the indoor Heat-Exchanger temperature is higher than 42°C, fan operates at seleted fan
speed, when it becomes lower than 39°C, the fan operates at low speed.
–10–
4. Heating Mode Operation (Except Cooling Model)
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Hot Start
Low
Selecting
Fan Speed
minimum 3min
Selecting fan
speed
minimum
10sec.
1min
A
A
minimum
1min.
minimum
10sec.
B
5. Hot-Start Control
• The indoor fan stops until the evaporator piping temperature will be reached to 28°C.
• The operation diagram is as following.
• The operation diagram is as following.
PIPING
TEMPERATURE
TEMPERATURE
1min
COMPRESSOR
INDOOR FAN
ON
28
°
C
: Selected Fan
: Low Fan
: Fan Stop
31
°
C
–11–
6. Defrost Control
• Defrost operation is controlled by timer and sensing the outdoor piping temperature.
• The defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from starting
• The defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from starting
of heating operation.
• Defrost ends after 10 minutes passed from starting of defrost operation or when the outdoor pipe
temperature rises over 12°C even if before 10 minutes.
More than 45 minutes of
heating operation
Outdoor Pipe Temp.
Indoor Fan
Compressor
4-Way Valve
ON
ON
ON
ON
OFF
ON
OFF
HOT-
START
ON
ON
OFF
OFF
ON
12
°
C
(Defrost OFF)
-6
°
C
(Defrost ON)
Within
10minutes
Defrost
Defrost
More than 45 minutes of
heating operation
7. Self-Diagnosis Function
• 'CHECK' will flash in the remote controller display when a problem occurs. Then please contact your dealer.
• Correct the accident point as shown in the table below before restarting operation.
• During the normal operation 'CHECK' won't be displayed in the remote controller.
• Correct the accident point as shown in the table below before restarting operation.
• During the normal operation 'CHECK' won't be displayed in the remote controller.
Remote controller LCD
Accident Point
F
1
Indoor temperature thermistor error
F2
Indoor piping thermistor error
F3
Indoor unit & remote controller
–11–
6. Defrost Control
• Defrost operation is controlled by timer and sensing the outdoor piping temperature.
• The defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from starting
• The defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from starting
of heating operation.
• Defrost ends after 10 minutes passed from starting of defrost operation or when the outdoor pipe
temperature rises over 12°C even if before 10 minutes.
More than 45 minutes of
heating operation
Outdoor Pipe Temp.
Indoor Fan
Compressor
4-Way Valve
ON
ON
ON
ON
OFF
ON
OFF
HOT-
START
ON
ON
OFF
OFF
ON
12
°
C
(Defrost OFF)
-6
°
C
(Defrost ON)
Within
10minutes
Defrost
Defrost
More than 45 minutes of
heating operation
7. Self-Diagnosis Function
• 'CHECK' will flash in the remote controller display when a problem occurs. Then please contact your dealer.
• Correct the accident point as shown in the table below before restarting operation.
• During the normal operation 'CHECK' won't be displayed in the remote controller.
• Correct the accident point as shown in the table below before restarting operation.
• During the normal operation 'CHECK' won't be displayed in the remote controller.
Remote controller LCD
Accident Point
F
1
Indoor temperature thermistor error
F2
Indoor piping thermistor error
F3
Indoor unit & remote controller