Harman Kardon SOUNDSTICKS III (serv.man2) EMC - CB Certificate ▷ View online
- Page 31 of 48 -
Report
No.
158002
TRF No.:IECEN60950_1C
Annex H
Replace the last paragraph of this annex by:
At any point 10 cm from the surface of the OPERATOR ACCESS AREA, the dose
rate shall not exceed 1 μSv/h (0,1 mR/h) (see NOTE). Account is taken of the
background level.
Replace the notes as follows:
At any point 10 cm from the surface of the OPERATOR ACCESS AREA, the dose
rate shall not exceed 1 μSv/h (0,1 mR/h) (see NOTE). Account is taken of the
background level.
Replace the notes as follows:
NOTE These values appear in Directive 96/29/Euratom.
Delete NOTE 2.
N/A
Biblio-
graphy
graphy
Additional EN standards.
—
ZA
NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH THEIR
CORRESPONDING EUROPEAN PUBLICATIONS
CORRESPONDING EUROPEAN PUBLICATIONS
—
ZB
SPECIAL NATIONAL CONDITIONS
—
1.2.4.1
In Denmark, certain types of Class I appliances (see 3.2.1.1) may be provided with
a plug not establishing earthing conditions when inserted into Danish socket-
outlets.
a plug not establishing earthing conditions when inserted into Danish socket-
outlets.
N/A
1.2.13.14
In Norway and Sweden, for requirements see 1.7.2.1 and 7.3 of this annex.
N/A
1.5.7.1
In Finland, Norway and Sweden, resistors bridging
BASIC INSULATION
in
CLASS I
PLUGGABLE EQUIPMENT TYPE A
must comply with the requirements in 1.5.7.1. In
addition when a single resistor is used, the resistor must withstand the resistor test
in 1.5.7.2.
in 1.5.7.2.
N/A
1.5.8
In Norway, due to the IT power system used (see annex V, Figure V.7), capacitors
are required to be rated for the applicable line-to-line voltage (230 V).
are required to be rated for the applicable line-to-line voltage (230 V).
N/A
1.5.9.4
In Finland, Norway and Sweden, the third dashed sentence is applicable only to
equipment as defined in 6.1.2.2 of this annex.
equipment as defined in 6.1.2.2 of this annex.
N/A
- Page 32 of 48 -
Report
No.
158002
TRF No.:IECEN60950_1C
1.7.2.1
In Finland, Norway and Sweden, CLASS I PLUGGABLE EQUIPMENT TYPE A
intended for connection to other equipment or a network shall, if safety relies on
connection to protective earth or if surge suppressors are connected between the
network terminals and accessible parts, have a marking stating that the equipment
must be connected to an earthed mains socket-outlet.
The marking text in the applicable countries shall be as follows:
In Finland: "Laite on liitettävä suojamaadoituskoskettimilla varustettuun
pistorasiaan"
In Norway: “Apparatet må tilkoples jordet stikkontakt”
In Sweden: “Apparaten skall anslutas till jordat nätuttak”
intended for connection to other equipment or a network shall, if safety relies on
connection to protective earth or if surge suppressors are connected between the
network terminals and accessible parts, have a marking stating that the equipment
must be connected to an earthed mains socket-outlet.
The marking text in the applicable countries shall be as follows:
In Finland: "Laite on liitettävä suojamaadoituskoskettimilla varustettuun
pistorasiaan"
In Norway: “Apparatet må tilkoples jordet stikkontakt”
In Sweden: “Apparaten skall anslutas till jordat nätuttak”
In Norway and Sweden, the screen of the cable distribution system is normally not
earthed at the entrance of the building and there is normally no equipotential
bonding system within the building. Therefore the protective earthing of the building
installation need to be isolated from the screen of a cable distribution system.
It is however accepted to provide the insulation external to the equipment by an
adapter or an interconnection cable with galvanic isolator, which may be provided
by e.g. a retailer.
The user manual shall then have the following or similar information in Norwegian
and Swedish language respectively, depending on in what country the equipment
is intended to be used in:
“Equipment connected to the protective earthing of the building installation through
the mains connection or through other equipment with a connection to protective
earthing – and to a cable distribution system using coaxial cable, may in some
circumstances create a fire hazard. Connection to a cable distribution system has
therefore to be provided through a device providing electrical isolation below a
certain frequency range (galvanic isolator, see EN 60728-11).”
earthed at the entrance of the building and there is normally no equipotential
bonding system within the building. Therefore the protective earthing of the building
installation need to be isolated from the screen of a cable distribution system.
It is however accepted to provide the insulation external to the equipment by an
adapter or an interconnection cable with galvanic isolator, which may be provided
by e.g. a retailer.
The user manual shall then have the following or similar information in Norwegian
and Swedish language respectively, depending on in what country the equipment
is intended to be used in:
“Equipment connected to the protective earthing of the building installation through
the mains connection or through other equipment with a connection to protective
earthing – and to a cable distribution system using coaxial cable, may in some
circumstances create a fire hazard. Connection to a cable distribution system has
therefore to be provided through a device providing electrical isolation below a
certain frequency range (galvanic isolator, see EN 60728-11).”
NOTE In Norway, due to regulation for installations of cable distribution systems, and in Sweden, a
galvanic isolator shall provide electrical insulation below 5 MHz. The insulation shall withstand a
dielectric strength of 1,5 kV r.m.s., 50 Hz or 60 Hz, for 1 min.
galvanic isolator shall provide electrical insulation below 5 MHz. The insulation shall withstand a
dielectric strength of 1,5 kV r.m.s., 50 Hz or 60 Hz, for 1 min.
Translation to Norwegian (the Swedish text will also be accepted in Norway):
“Utstyr som er koplet til beskyttelsesjord via nettplugg og/eller via annet jordtilkoplet
utstyr – og er tilkoplet et kabel-TV nett, kan forårsake brannfare. For å unngå dette
skal det ved tilkopling av utstyret til kabel-TV nettet installeres en galvanisk isolator
mellom utstyret og kabel- TV nettet.”
Translation to Swedish:
”Utrustning som är kopplad till skyddsjord via jordat vägguttag och/eller via annan
utrustning och samtidigt är kopplad till kabel-TV nät kan i vissa fall medfőra risk főr
brand. Főr att undvika detta skall vid anslutning av utrustningen till kabel-TV nät
galvanisk isolator finnas mellan utrustningen och kabel-TV nätet.”
“Utstyr som er koplet til beskyttelsesjord via nettplugg og/eller via annet jordtilkoplet
utstyr – og er tilkoplet et kabel-TV nett, kan forårsake brannfare. For å unngå dette
skal det ved tilkopling av utstyret til kabel-TV nettet installeres en galvanisk isolator
mellom utstyret og kabel- TV nettet.”
Translation to Swedish:
”Utrustning som är kopplad till skyddsjord via jordat vägguttag och/eller via annan
utrustning och samtidigt är kopplad till kabel-TV nät kan i vissa fall medfőra risk főr
brand. Főr att undvika detta skall vid anslutning av utrustningen till kabel-TV nät
galvanisk isolator finnas mellan utrustningen och kabel-TV nätet.”
N/A
1.7.5
In Denmark, socket-outlets for providing power to other equipment shall be in
accordance with the Heavy Current Regulations, Section 107-2-D1, Standard
Sheet DK 1-3a, DK 1-5a or DK 1-7a, when used on Class I equipment. For
STATIONARY EQUIPMENT the socket-outlet shall be in accordance with Standard
Sheet DK 1-1b or DK 1-5a.
For
accordance with the Heavy Current Regulations, Section 107-2-D1, Standard
Sheet DK 1-3a, DK 1-5a or DK 1-7a, when used on Class I equipment. For
STATIONARY EQUIPMENT the socket-outlet shall be in accordance with Standard
Sheet DK 1-1b or DK 1-5a.
For
CLASS II EQUIPMENT
the socket outlet shall be in accordance with Standard
Sheet DKA 1-4a.
N/A
2.2.4
In Norway, for requirements see 1.7.2.1, 6.1.2.1 and 6.1.2.2 of this annex.
N/A
- Page 33 of 48 -
Report
No.
158002
TRF No.:IECEN60950_1C
2.3.2
In Finland, Norway and Sweden there are additional requirements for the
insulation. See 6.1.2.1 and 6.1.2.2 of this annex.
insulation. See 6.1.2.1 and 6.1.2.2 of this annex.
N/A
2.3.4
In Norway, for requirements see 1.7.2.1, 6.1.2.1 and 6.1.2.2 of this annex.
N/A
2.6.3.3
In the United Kingdom, the current rating of the circuit shall be taken as 13 A, not
16 A.
16 A.
N/A
2.7.1
In the United Kingdom, to protect against excessive currents and short-circuits in
the PRIMARY CIRCUIT of DIRECT PLUG-IN EQUIPMENT, tests according to 5.3
shall be conducted, using an external protective device rated 30 A or 32 A. If these
tests fail, suitable protective devices shall be included as integral parts of the
DIRECT PLUG-IN EQUIPMENT, so that the requirements of 5.3 are met.
the PRIMARY CIRCUIT of DIRECT PLUG-IN EQUIPMENT, tests according to 5.3
shall be conducted, using an external protective device rated 30 A or 32 A. If these
tests fail, suitable protective devices shall be included as integral parts of the
DIRECT PLUG-IN EQUIPMENT, so that the requirements of 5.3 are met.
N/A
2.10.5.13
In Finland, Norway and Sweden, there are additional requirements for the
insulation, see 6.1.2.1 and 6.1.2.2 of this annex.
insulation, see 6.1.2.1 and 6.1.2.2 of this annex.
N/A
3.2.1.1
In Switzerland, supply cords of equipment having a RATED CURRENT not
exceeding 10 A shall be provided with a plug complying with SEV 1011 or IEC
60884-1 and one of the following dimension sheets:
SEV 6532-2.1991 Plug Type 15
exceeding 10 A shall be provided with a plug complying with SEV 1011 or IEC
60884-1 and one of the following dimension sheets:
SEV 6532-2.1991 Plug Type 15
3P+N+PE 250/400 V, 10 A
SEV 6533-2.1991 Plug Type 11
L+N
250 V, 10 A
SEV 6534-2.1991 Plug Type 12
L+N+PE
250 V, 10 A
In general, EN 60309 applies for plugs for currents exceeding 10 A. However, a 16
A plug and socket-outlet system is being introduced in Switzerland, the plugs of
which are according to the following dimension sheets, published in February
1998:
SEV 5932-2.1998 Plug Type 25
A plug and socket-outlet system is being introduced in Switzerland, the plugs of
which are according to the following dimension sheets, published in February
1998:
SEV 5932-2.1998 Plug Type 25
3L+N+PE 230/400 V, 16 A
SEV 5933-2.1998 Plug Type 21
L+N
250 V, 16 A
SEV 5934-2.1998 Plug Type 23
L+N+PE
250 V, 16 A
N/A
3.2.1.1
In Denmark, supply cords of single-phase equipment having a rated current not
exceeding13 A shall be provided with a plug according to the Heavy Current
Regulations, Section 107-2-D1.
CLASS I EQUIPMENT provided with socket-outlets with earth contacts or which
are intended to be used in locations where protection against indirect contact is
required according to the wiring rules shall be provided with a plug in accordance
with standard sheet DK 2-1a or DK 2-5a.
If poly-phase equipment and single-phase equipment having a RATED CURRENT
exceeding 13 A is provided with a supply cord with a plug, this plug shall be in
accordance with the Heavy Current Regulations, Section 107-2-D1 or EN 60309-2.
exceeding13 A shall be provided with a plug according to the Heavy Current
Regulations, Section 107-2-D1.
CLASS I EQUIPMENT provided with socket-outlets with earth contacts or which
are intended to be used in locations where protection against indirect contact is
required according to the wiring rules shall be provided with a plug in accordance
with standard sheet DK 2-1a or DK 2-5a.
If poly-phase equipment and single-phase equipment having a RATED CURRENT
exceeding 13 A is provided with a supply cord with a plug, this plug shall be in
accordance with the Heavy Current Regulations, Section 107-2-D1 or EN 60309-2.
N/A
3.2.1.1
In Spain, supply cords of single-phase equipment having a rated current not
exceeding 10 A shall be provided with a plug according to UNE 20315:1994.
Supply cords of single-phase equipment having a rated current not exceeding 2,5
A shall be provided with a plug according to UNE-EN 50075:1993.
CLASS I EQUIPMENT provided with socket-outlets with earth contacts or which
are intended to be used in locations where protection against indirect contact is
required according to the wiring rules, shall be provided with a plug in accordance
with standard UNE 20315:1994.
If poly-phase equipment is provided with a supply cord with a plug, this plug shall
be in accordance with UNE-EN 60309-2.
exceeding 10 A shall be provided with a plug according to UNE 20315:1994.
Supply cords of single-phase equipment having a rated current not exceeding 2,5
A shall be provided with a plug according to UNE-EN 50075:1993.
CLASS I EQUIPMENT provided with socket-outlets with earth contacts or which
are intended to be used in locations where protection against indirect contact is
required according to the wiring rules, shall be provided with a plug in accordance
with standard UNE 20315:1994.
If poly-phase equipment is provided with a supply cord with a plug, this plug shall
be in accordance with UNE-EN 60309-2.
N/A
- Page 34 of 48 -
Report
No.
158002
TRF No.:IECEN60950_1C
3.2.1.1
In the United Kingdom, apparatus which is fitted with a flexible cable or cord and
is designed to be connected to a mains socket conforming to BS 1363 by means of
that flexible cable or cord and plug, shall be fitted with a ‘standard plug’ in
accordance with Statutory Instrument 1768:1994 - The Plugs and Sockets etc.
(Safety) Regulations 1994, unless exempted by those regulations.
is designed to be connected to a mains socket conforming to BS 1363 by means of
that flexible cable or cord and plug, shall be fitted with a ‘standard plug’ in
accordance with Statutory Instrument 1768:1994 - The Plugs and Sockets etc.
(Safety) Regulations 1994, unless exempted by those regulations.
NOTE ‘Standard plug’ is defined in SI 1768:1994 and essentially means an approved plug
conforming to BS 1363 or an approved conversion plug.
conforming to BS 1363 or an approved conversion plug.
N/A
3.2.1.1
In Ireland, apparatus which is fitted with a flexible cable or cord and is designed to
be connected to a mains socket conforming to I.S. 411 by means of that flexible
cable or cord and plug, shall be fitted with a 13 A plug in accordance with Statutory
Instrument 525:1997 - National Standards Authority of Ireland (section 28) (13 A
Plugs and Conversion Adaptors for Domestic Use) Regulations 1997.
be connected to a mains socket conforming to I.S. 411 by means of that flexible
cable or cord and plug, shall be fitted with a 13 A plug in accordance with Statutory
Instrument 525:1997 - National Standards Authority of Ireland (section 28) (13 A
Plugs and Conversion Adaptors for Domestic Use) Regulations 1997.
N/A
3.2.4
In Switzerland, for requirements see 3.2.1.1 of this annex.
N/A
3.2.5.1
In the United Kingdom, a power supply cord with conductor of 1,25 mm2 is
allowed for equipment with a rated current over 10 A and up to and including 13 A.
allowed for equipment with a rated current over 10 A and up to and including 13 A.
N/A
3.3.4
In the United Kingdom, the range of conductor sizes of flexible cords to be
accepted by terminals for equipment with a RATED CURRENT of over 10 A up to
and including 13 A is:
• 1,25 mm
accepted by terminals for equipment with a RATED CURRENT of over 10 A up to
and including 13 A is:
• 1,25 mm
2
to 1,5 mm
2
nominal cross-sectional area.
N/A
4.3.6
In the United Kingdom, the torque test is performed using a socket outlet
complying with BS 1363 part 1:1995, including Amendment 1:1997 and
Amendment 2:2003 and the plug part of DIRECT PLUG-IN EQUIPMENT shall be
assessed to BS 1363: Part 1, 12.1, 12.2, 12.3, 12.9, 12.11, 12.12, 12.13, 12.16 and
12.17, except that the test of 12.17 is performed at not less than 125 °C. Where the
metal earth pin is replaced by an Insulated Shutter Opening Device (ISOD), the
requirements of clauses 22.2 and 23 also apply.
complying with BS 1363 part 1:1995, including Amendment 1:1997 and
Amendment 2:2003 and the plug part of DIRECT PLUG-IN EQUIPMENT shall be
assessed to BS 1363: Part 1, 12.1, 12.2, 12.3, 12.9, 12.11, 12.12, 12.13, 12.16 and
12.17, except that the test of 12.17 is performed at not less than 125 °C. Where the
metal earth pin is replaced by an Insulated Shutter Opening Device (ISOD), the
requirements of clauses 22.2 and 23 also apply.
N/A
4.3.6
In Ireland, DIRECT PLUG-IN EQUIPMENT is known as plug similar devices. Such
devices shall comply with Statutory Instrument 526:1997 - National Standards
Authority of Ireland (Section 28) (Electrical plugs, plug similar devices and sockets
for domestic use) Regulations, 1997.
devices shall comply with Statutory Instrument 526:1997 - National Standards
Authority of Ireland (Section 28) (Electrical plugs, plug similar devices and sockets
for domestic use) Regulations, 1997.
N/A
5.1.7.1
In Finland, Norway and Sweden TOUCH CURRENT measurement results
exceeding 3,5 mA r.m.s. are permitted only for the following equipment:
• STATIONARY PLUGGABLE EQUIPMENT TYPE A that
exceeding 3,5 mA r.m.s. are permitted only for the following equipment:
• STATIONARY PLUGGABLE EQUIPMENT TYPE A that
○
is intended to be used in a RESTRICTED ACCESS LOCATION
where
equipotential bonding has been applied, for example, in a
telecommunication
centre;
and
○
has provision for a permanently connected PROTECTIVE
EARTHING
CONDUCTOR;
CONDUCTOR;
and
○
is provided with instructions for the installation of that conductor by a
SERVICE
PERSON;
• STATIONARY PLUGGABLE EQUIPMENT TYPE B;
• STATIONARY PERMANENTLY CONNECTED EQUIPMENT.
• STATIONARY PERMANENTLY CONNECTED EQUIPMENT.
N/A
Click on the first or last page to see other SOUNDSTICKS III (serv.man2) service manuals if exist.